Products

Clēēr™ 600 A Loadbreak Connector System

cleer-600A-loadbreak.jpg

Clēēr™ Loadbreak Connector reduces outages by providing reliable switching under load – as reliable as traditional 200A loadbreak connectors – and allows other circuits to remain energized, limiting the amount of downtime and inconvenienced customers.

It is the only 600A/15 kV three-phase rated loadbreak connector system in the industry. This unique solution offers both a visible break and visible ground without having to de-energize, unbolt 600A terminations, or move heavy cables. This system offers an efficient and reliable visible break when used for sectionalizing, splicing, or in-line with vacuum switchgear.

Continuous Current 600 A rms
Loadbreak Switching Ten make and break operations at 600 A at 14.4 kV Phase-Phase
Loadbreak Switching Three make and break operations at 900 A at 14.4 kV Phase-Phase
Fault Closure 16 kA rms symmetrical at 14.4 kV Phase-Phase after ten 600 A loadbreak switching operations for 0.17 seconds
Fault Closure 16 kA rms symmetrical at 14.4 kV Phase-Phase after three 900 A loadbreak switching operations for 0.17 seconds
4 Hour Overload Current 900 A rms
Short Time Current 16 kA rms symmetrical for 0.17 seconds (limited by fault closure rating)
Short Time Current 10 kA rms symmetrical for 3.0 seconds

Features

  • C-shape Clēēr Loadbreak Connector is tested for ten loadbreak and loadmake operations at 600 A and three loadbreak and loadmake operations at 900 A with a 16 kA fault close rating for 0.17 seconds.
    • The C-shaped connector breaks the circuit in two places for twice the contact separation.
  • The new Clēēr Loadbreak Connector incorporates field-proven Cooper Power Systems POSI-BREAK™ technology which provides:
    • Increased strike distance, greatly reducing the possibility of partial vacuum flashovers
    • Added dielectric strength along the probes for superior switching performance and reliability
  • The remainder of this simple system consists of:
    • Two Cooper Power Systems 600 A loadbreak interfaces
    • Two IEEE Std 386™-2006 standard 600 A deadbreak interfaces
  • A yellow latch indicator is included to assure positive connection
  • Fully submersible, and exceeds the applicable requirements of IEEE Std 386™-2006 standard for use in above- and underground environments prone to flooding
  • When using BT-TAP or T-OP II connectors a visible ground can be achieved by connecting a grounding elbow directly to a 200 A loadbreak reducing tap plug.